Vacuum breakers sit at least 12 inches above the highest outlet. RPs stay above grade so they can drain. Every install leaves room for yearly testing.
Same-week visits. Price before any work.
- PriceFree quote
- TimeUsually 1 day
- TestIncluded
- FilingIncluded
Installation rules we follow
- Vacuum breakers above the highest downstream outlet
- Clearance for testers and repairs
- RP assemblies above grade, never in a pit
- Freeze and theft protection where needed
Where an assembly should go
Where an assembly sits affects whether it can work and whether it passes inspection. RP assemblies must be installed above ground, with enough space under them for the relief valve to drain freely. Putting an RP in a pit or a box that floods is one of the most common mistakes we see.
Pressure vacuum breakers and spill-resistant vacuum breakers have to be higher than the highest sprinkler head or outlet they protect, usually by at least 12 inches. On hillside lots, that can mean placing the device near the top of the yard instead of by the meter.
Double checks have more flexibility and are sometimes placed in vaults, especially on fire lines, but they still need room to be tested and repaired.
Leaving room to test and service
Since every assembly gets tested yearly, it has to be easy to reach. Testers need space for the gauge hoses at the test cocks, room to turn the shutoffs, and enough clearance to open the checks for repairs.
A device crammed against a wall, hidden in bushes or tucked into a tight ceiling space can make a quick test drag on, or make a repair require cutting pipe. We plan the install so that doesn't happen.
Access for testers matters too. Behind a gate is fine at a house. At a business, a spot testers can reach without an escort saves everyone time.
Freeze and theft protection
Freezes aren't common here, but inland and higher areas can get a cold snap that cracks a brass body or bonnet in one night. Insulated covers or enclosures help where that's a risk.
Theft is often the bigger threat. Brass devices near streets and lots attract scrap thieves, and a stolen device means an open line and a rush repair. A locking cage on a concrete pad is the standard fix.
We'll suggest protection based on the location, and a cage or cover can be included in your installation quote.
Finishing the job
Once an assembly is installed and the lines are flushed, we run the startup test. This is the same procedure used each year, and it confirms the device was installed correctly and works as designed.
The passing report is filed with your water district, which adds the device to its records and sets the first annual due date. You get a copy for your files.
From then on, the device needs an annual test. We can remind you before it's due, or you can add due date management and we'll handle the scheduling every year.
Fixing a poorly placed device
Sometimes an existing device just isn't in the right place. RPs below ground, PVBs lower than the sprinklers and devices with no room for testing are common examples.
Moving it means new piping and a retest afterward. If the device itself is still good, we can usually reuse it to save you money.
Working with contractors
On new construction and remodels, backflow installation is one piece of a bigger schedule. We work with general contractors, plumbers and landscape contractors to install the assembly when the site is ready and test it when water is available.
The startup test report is often needed for final inspection, so we make sure it's filed in time.
Choosing materials and fittings
The assembly is only as good as what connects it. We use fittings rated for potable water and sized to match the device, with unions where they make future repairs easier. Larger assemblies get proper supports so the weight isn't hanging on the pipe.
Outdoor devices near sprinklers or soil get fittings that hold up to the weather. These details don't show on the test report, but they're the difference between an install that lasts and one that leaks in a few years.
After installation
The first test and report are included. From then on, plan on an annual test.
Questions
Can an RP go underground?
No. The relief valve has to drain, so RPs go above ground.
Can you move an existing assembly?
Yes. A moved assembly has to be retested afterward, and we include that.
How long does installation take?
Most installs for 2-inch and smaller assemblies take a day.
Do you add a cage or cover?
If theft or freezing is a risk, we recommend one and include it in the quote.
Do you pour a pad for a cage?
Yes, when a cage is part of the job we include the pad it bolts to.
Can a PVB go next to the meter?
Only if the meter is higher than every sprinkler it protects. On sloped yards it often needs to go uphill.
Why Temecula customers call us
Certified testers, calibrated gauges and district filing on every job. You get the price before any work and a copy of every report.
Testing is $105 per device under 4 inches and $175 for 4 inches and up. Other work is quoted free. Phones are answered 7 days a week, 6am to midnight, and emergency calls 24/7. Most visits are booked within the week.
A typical visit in Temecula: a confirmation call the day before, under an hour on site for the test, and the report filed the same day. When a test fails, the fix is usually a rebuild kit, done in one to two hours with the retest included. Bigger jobs like replacements and new installs get a free written quote first. Every report we file is also emailed to you, so your records stay complete.
Where we offer it
We provide backflow assembly installation in Temecula, Murrieta, Rainbow, French Valley and Pala. Typical wait: under a week.