We check leaks, damage, drainage, height and clearance on every device we test. If something needs work, you get a written note and a price.
Same-week visits. Price before any work.
- Price$105 flat
- TimeUnder an hour
- SchedulingSame week
- FilingIncluded
What an inspection covers
- Condition of the valves and fittings
- Signs of leaks or past freeze damage
- Room to test and service the device
- Whether an RP can drain properly
- Cage or cover condition
How an inspection differs from a test
A backflow test answers one question: do the valves hold when measured with a gauge? An inspection answers a wider one: is this device in good condition and installed in a way that lets it keep working and be tested every year?
A device can pass its readings and still have problems. It might be leaking from a fitting, missing a test cock cap, sitting in a pit where an RP isn't allowed, or wedged so tightly against a wall that the next tester can't reach it. Those issues don't show up in the numbers.
That's why we look over the device and its surroundings on every visit. Anything worth knowing gets noted, along with whether it needs attention now or can wait.
Setup issues that cause trouble later
A lot of issues trace back to the original install. RPs need to sit above grade so the relief valve can dump water freely. If one is in a vault or a box that fills with water, it can't do its job.
PVBs and SVBs have to be higher than the sprinklers they protect. Hillside yards make this easy to get wrong, with heads above the device.
Other finds include devices installed in the wrong direction, devices crammed into spaces too tight to test, and shutoff valves that don't seal. All of these are fixable, and we'll walk you through what it would take.
Signs of wear and damage
Older devices give clues before they fail. Green or white crust around fittings points to slow leaks. A relief valve that drips between uses suggests a fouled or worn check. Corrosion on bolts and covers can make future repairs harder.
We also look for freeze damage, which shows up as cracks in the body or bonnet, and impact damage from mowers, vehicles or landscaping crews. Missing caps on test cocks let dirt in and can affect future readings.
Theft is a growing problem with brass devices. If yours is exposed near a street or parking area, we may suggest a locking cage. We'll tell you which of these things matter now and which can be handled at next year's test.
Times to ask for an inspection
We inspect on every test, but sometimes an inspection alone is what you need. Buyers of commercial properties often want one before closing. Managers taking over a new building like to know what's there.
Other good times include after a freeze, after nearby construction or landscaping, and after the device has been bumped or hit.
Give us a call and describe the situation. If the device is close to its due date, we'll usually combine the inspection with the annual test so you get both the report and the condition check in one trip.
Where the water goes
RP assemblies are designed to discharge water from the relief valve when something goes wrong. That water has to go somewhere. If an RP is mounted indoors without a drain, or outdoors where discharge floods a walkway or parking lot, a small problem can cause bigger damage.
We look at where discharge would go and whether the drain or grading can handle it. If not, we'll suggest options like an air gap drain funnel or relocating the device.
How we report what we found
Our notes are short and plain. Each item says what we saw, why it matters and whether it needs attention now, soon or just at next year's test.
If anything needs repair, you'll get a price with it. We avoid padding the list with minor items, so what's on it is worth reading. Property managers often forward the notes straight to owners or boards for approval.
Inspection for buyers
Backflow devices often get missed during a property purchase, and replacing several isn't cheap. That's especially true for commercial buildings, apartments and homes with pools, sprinklers or fire systems.
A pre-closing inspection shows how many devices are on site, their condition and whether any are the wrong type or near the end of their life. It's helpful for negotiating and for budgeting your first year.
If something needs work
We'll tell you what we saw and whether it needs a repair or can wait.
Questions
Is an inspection the same as a test?
No. The test measures how the valves perform. The inspection looks at the device's condition and setup. We do both on every visit.
Do you inspect devices you didn't install?
Yes. We inspect every device we test, no matter who put it in.
Will you send me what you found?
Yes. Anything worth noting goes in writing with your report.
Will an inspection fix the problems it finds?
No, but we'll explain each issue and give you a price for any repair.
Can an inspection catch problems before a test fails?
Often, yes. Leaks, worn parts and bad drainage show up before the readings drop.
Does the inspection cost extra?
It's part of every test we do. Call if you need an inspection on its own.
Why Temecula customers call us
Certified testers, calibrated gauges and district filing on every job. You get the price before any work and a copy of every report.
Testing is $105 per device under 4 inches and $175 for 4 inches and up. Other work is quoted free. Phones are answered 7 days a week, 6am to midnight, and emergency calls 24/7. Most visits are booked within the week.
A typical visit in Temecula: a confirmation call the day before, under an hour on site for the test, and the report filed the same day. When a test fails, the fix is usually a rebuild kit, done in one to two hours with the retest included. Bigger jobs like replacements and new installs get a free written quote first. Every report we file is also emailed to you, so your records stay complete.
Where we offer it
We provide backflow inspection in Temecula, Murrieta, Rainbow, French Valley and Pala. Typical wait: under a week.